More Versatility
- Integrated with PV/ESS/D.G. for comprehensive scenarios
- LV Compatible, seamless on/off-Grid switching
- Compatible with mainstream standardized protocols

Solutions & Products
DC coupling increases cycle efficiency by 3-5%, with seamless on/off-grid switching for greater solar utilization.
PRODUCT SPECIFICATIONS
| Battery System Capacity | Dimensions (W*D*H) | Rated Power | AC Current Harmonics (THDi) |
| 261.12kWh | 1474x1320x2285±5mm | 125kW | <3% (Rated Output Power) |
| Cell Type | Weight | Maximum Output Power | Access Mode |
| LFP3.2V/314Ah | 2700kg | 138kW | Three-phase Four-wire |
| Battery System Configuration | Ingress Protection Rating | Maximum Output Current | Maximum Input Power |
| 1P268S | IP54 | 200A | 63kW*2 |
| Rated Charge/Discharge Rate | Noise Level | Rated Grid Voltage | Maximum Input Current |
| 0.5P | ≤75dB@1m | 230/400V AC | 160A |
| Nominal Voltage | System Efficiency | Rated Grid Frequency | Full-Power Voltage Range |
| 832V | ≥89% | 50/60Hz, ±5Hz | 573V~1000V |
| Battery Voltage Range | System Design Life | Power Factor | High-Side Starting Voltage |
| 704V~936V | ≥15年 | -1 (Leading) ~ 1 (Lagging) | 280V~1000V |
| Allowable Ambient Temperature | Fire Protection Solution | ||
| -20℃~50℃ (> 45℃ Derating Required) | Smoke Detector, Temperature Detector, Pack-Level Fire Protection, Cabin-Level Fire Protection, Aerosol Fire Suppression | ||
| Allowable Ambient Humidity | Communication Interface / Communication Protocol | ||
| 0~95% (Non-condensing) | Ethernet, RS485, CAN | ||
| Maximum Operating Altitude | Communication Protocol | ||
| ≤2000m | Modbus RTU, Modbus TCP, CAN 2.0B, IEC 61850 | ||
| Thermal Management Method | Certifications | ||
| Intelligent Liquid Cooling | IEC 62619, IEC 62477-1, IEC 61000, IEC 62109, IEC 62933, UL 9540A, UN 38.3 | ||