Solutions & Products

JANUS-261PV+

DC coupling increases cycle efficiency by 3-5%, with seamless on/off-grid switching for greater solar utilization.

More Versatility

  • Integrated with PV/ESS/D.G. for comprehensive scenarios
  • LV Compatible, seamless on/off-Grid switching
  • Compatible with mainstream standardized protocols

PRODUCT SPECIFICATIONS

Battery System CapacityDimensions (W*D*H)Rated PowerAC Current Harmonics (THDi)
261.12kWh1474x1320x2285±5mm125kW<3% (Rated Output Power)
Cell TypeWeightMaximum Output PowerAccess Mode
LFP3.2V/314Ah2700kg138kWThree-phase Four-wire
Battery System ConfigurationIngress Protection RatingMaximum Output CurrentMaximum Input Power
1P268SIP54200A63kW*2
Rated Charge/Discharge RateNoise LevelRated Grid VoltageMaximum Input Current
0.5P≤75dB@1m230/400V AC160A
Nominal VoltageSystem EfficiencyRated Grid FrequencyFull-Power Voltage Range
832V≥89%50/60Hz, ±5Hz573V~1000V
Battery Voltage RangeSystem Design LifePower FactorHigh-Side Starting Voltage
704V~936V≥15年-1 (Leading) ~ 1 (Lagging)280V~1000V
Allowable Ambient TemperatureFire Protection Solution
-20℃~50℃ (> 45℃ Derating Required)Smoke Detector, Temperature Detector, Pack-Level Fire Protection, Cabin-Level Fire Protection, Aerosol Fire Suppression
Allowable Ambient HumidityCommunication Interface / Communication Protocol
0~95% (Non-condensing)Ethernet, RS485, CAN
Maximum Operating AltitudeCommunication Protocol
≤2000mModbus RTU, Modbus TCP, CAN 2.0B, IEC 61850
Thermal Management MethodCertifications
Intelligent Liquid CoolingIEC 62619, IEC 62477-1, IEC 61000, IEC 62109, IEC 62933, UL 9540A, UN 38.3

JANUS-261PV+

To download the product datasheet, please click the button below.

LET'S CONNECTHave an energy project in mind?global@lisiner.comSend an inquiry